High-Temp Industries offers a wide variety of digital temperature and process controllers with simplistic interfaces that are preferred by most operators. All devices provide auto on/off, soft start, auto-tune for easy setup, advanced control algorithms to limit overshoot, fuzzy logic, multiple output configurations and have fully-programmable functions. Compare to Athena, Omron and Omega. Feature a 3-year warranty for manufacturing defects. Please Click Here for Further Information and Current Pricing.



All sizes are just $99!
Models:
- 1/16 DIN - 48x48mm, 150g
- 1/8 DIN - 96x48mm, 225g
- 1/4 DIN - 96x96mm, 300g
Common Technical Specifications:
- Power: AC 85-265V DC 24V
- Power Consumption: 4VA
- Frequency: 50/60Hz
- Memory: Power Disconnect Preserve Memory E2Prom
- Input: Sensing Signal
- Sample Time: 240mS with Display Accuracy of .2% of FS.
- Thermocouple: K, J, R, S, B, E, N, T, W, PL2, U, L
- RTD: DPT100, JPT100, JPT50
- Linear Current (mA): 4~20mA, 0~20mA
- Linear Voltage (mV, V): 0~1V, 0~5V, 0~10V, 1~5V 2~10V, -10~10mV, 0~10mV, 0~20mV, 0~50mV, 10~50mV
- Location for Decimal Point: 0000, 00.0, 00.00, 0.000 (Input of Linear Current and Voltage)
- Output: Control Model (Heat or Cool Model)
- Relay: 3A, 220V, Electric Life of 100,000 times or more under rated load.
- Pulse Voltage: Use for SSR ON=24V, OFF=0V, Largest Load is 20mA
- Linear Current (mA): 4~20mA, 0~20mA, Largest Load is 560?
- Linear Voltage (V): 0~1V, 0~5V, 0~10V, 1~5V 2~10V, -10~10mV, 0~10mV, 0~20mV, 0~50mV, 10~50mV
- First Group Alarm: 3A, 220V, Electric Life of 100,000 times or more under rated load.
- Second Group Alarm: 3A, 220V, Electric Life of 100,000 times or more under rated load.
- Third Group Alarm: 3A, 220V, Electric Life of 100,000 times or more under rated load.
- Control Mode: PID, P, PI, PD, ON/OFF (P=0) and FUZZY
- PID Setting Range: P: 0~200% I: 0~3,600 (S) D: 0~900 (S)
- Insulation: Control Loop (Control Output, Alarm, Transit Output, and Input Loop)
- Insulating Resistance: Main Loop~Crust (Ground) DC 500V>10M?; Control Loop~Crust (Ground) DC50V>10M?
- Voltage Resistance: Main Loop~Crust (Ground) 1,500V per Minute; Control Loop~Crust (Ground) 1,000V per Minute
- Operating Environment: 0~50oC @ 50~85% Relative Humidity
- Communication: RS232, RS484
- Communication Rate: 9600, 4800, 2400, 1200, 300, 110bps; Outset Bit 1, Stop Bit, Odd Parity
- Protection: Waterproof and Dustproof (NEMA A4)